Hager EUD100 is a voltage and phase monitoring relay intended for use in single- and three-phase supply systems in the 1P+N or 3P+N configuration. It is installed in distribution boards of residential, commercial, and technical facilities to monitor the condition of the mains and disconnect the load when the supply voltage moves outside the permissible range or when the phase regime is disturbed. Such operation helps protect connected equipment from abnormal operating conditions and supports automatic reconnection after the network parameters return to normal.
The device is designed for alternating current. The rated supply and operating voltage is 230–400 V at both 50 Hz and 60 Hz. The voltage measuring range is 161–520 V, while the 230–400 V range is also specified as a control range in the operating mode. The relay provides a minimum adjustable switching-off time of 0.1 s and a maximum permissible switching-off time of 10 s, allowing the response speed to be adapted to the characteristics of the installation. The switching-on delay is adjustable from 10 to 600 s, which reduces the risk of repeated switching after short-term supply disturbances.
EUD100 has one changeover contact and uses screw connection for electrical termination. This terminal type is suitable for fixed installation in a switchboard and provides straightforward conductor connection. The relay does not require an external power supply, which simplifies integration into the circuit and reduces the number of additional components needed for operation.
The compact housing measures 17.5 mm in width, 65 mm in depth, and 87 mm in height, so the relay occupies little space on a DIN rail and fits well into enclosures with limited mounting room. The device also features hysteresis for both single-phase and three-phase operation, which supports stable switching behavior within the monitored voltage limits.
This relay does not support DC voltage monitoring and is not specified as a dedicated single-phase or three-phase overvoltage/undervoltage protection device in the listed modes. Its purpose is the basic monitoring of voltage and phase conditions in AC networks, with timely disconnection of the load when abnormal deviations occur.